  • Equipped with the ACVMax burner and modbus controls.
  • Total Condensing unit - condenses in both heating and hot water mode.
  • Can provide heating and hot water or can be used as a stand alone hot water generator.
  • Can deliver an exceptional peak and continuous volume of hot water.
  • Stainless Steel domestic hot water tank - no glass lined steel or anode protection required.
  • Space saving footprint - Heating and hot water from one unit reduces plantroom space requirements.
  • Stainless steel heat exchanger reduces maintenance and can increase system lifespan.
  • Floor standing boiler with large volume of primary water, ideal for existing heating systems.
  • Multiple units can be linked for larger applications or back up
  • Can be installed along with Prestige heat only boilers or Smart cylinders to provide a perfect solution to your heating and hot water requirements.
Schematic
  1. Concentric flue gas/air inlet box
  2. Flue gas exhaust tube
  3. Combustion chamber
  4. Stainless steel heat exchanger
  5. Stainless steel “Tank-in-Tank” hot water production tank (primary + DHW)
  6. Primary circuit separation disc
  7. Indirect water pre-heater
  8. Insulation
  9. Condensate recovery dish + NTC5 sensor (flue gas)
  10. High efficiency circulator pump
  11. NTC2 sensor (CH return)
  12. Electrical panel (with spare fuses at the back)
  13. ACVMax Touch Control panel
  14. On-Off switch
  15. DHW tank dry well (Dip tube with temperature sensor)
  16. Automatic air vent
  17. Gas pressure switch
  18. NTC1 sensor (CH supply)
  19. Gas valve
  20. DHW safety valve / (T & P relief valve - UK only)
  21. Modulating air/gas premix burner with fan
  22. Air inlet

Constructive characteristics

HeatMaster 70 TC Evo HeatMaster 85 TC Evo HeatMaster 120 TC Evo
Capacity (total) L 315 315 315 L
Capacity (primary) L 125 125 125 L
Capacity (domestic hot water) L 190 190 190 L
Chimney: Max pressure drop in flue pipe Pa 150 150 170 Pa
Chimney: max length of concentric flue pipe m 22 22 21 m
Chimney connection Ømm 100/150 100/150 100/150 Ømm
Connection - heating Ø" 1 ½ F 1 ½ F 1 ½ F Ø"
Connection - DHW Ø" 1 M 1 M 1 M Ø"
Connection gas Ø" 3/4 M 3/4 M 3/4 M Ø"
Connection - safety valve Ø" 1/2 M 1/2 M 1/2 M Ø"
Max operating temperature °C 87 87 87 °C
Water pressure drop boiler at Δt = 20°C mbar 9 14 27 mbar
Max service pressure heating (primary) bar 3 3 3 bar
Max service pressure (DHW) bar 8,6 8,6 8,6 bar
Pressure drop (primary - ΔT10K) mbar 9,3 - - mbar
Height when tilted mm 2270 2270 2270 mm
Weight (empty) kg 298 298 299 kg

Heating characteristics

HeatMaster 70 TC Evo HeatMaster 85 TC Evo HeatMaster 120 TC Evo
Pre-heating time from 10 to 80°C (Heat source: boiler) min 27 24 23 min
Reheat time from 40 to 90°C min 37 36 30 min
Reheat time from 40 to 80°C min 18 16 15 min
Heating time from 10 to 90°C min 47 43 38 min

Combustion

HeatMaster 70 TC Evo HeatMaster 85 TC Evo HeatMaster 120 TC Evo
Input max (heating) HCV kW 77,6 94,4 127,7 kW
Input max (heating) LCV kW 69,9 85,0 115,0 kW
Combustion efficiency % 98,1 98 97,5 %
Efficiency at 30% load (EN15502-1) % 109,0 108 108 %
Efficiency at 100% load (50/30°C) % 105,8 105,8 105,8 %
Efficiency (max output) 80/60°C % 97,3 97 97 %
Efficiency (min output) 80/60°C % 97,3 97,5 97,1 %
Efficiency DHW mode ΔT 30K % 103,9 103,9 102,2 %
CO emissions max output ppm 34 51 50 ppm
CO emissions min output ppm 7 6 4 ppm
Mass rate of combustion products (gas) kg/h 114 111 183 kg/h
NOx weighted (GCV) (EN15502) mg/kWh 33,1 29,3 39,8 mg/kWh
NOx class (EN15502) 6 6 6
Output power max (80/60°C) kW 68,0 82,9 111,7 kW
Output power min (80/60°C) kW 20,9 20,5 22,9 kW
Output power max (50/30°C) kW 74,0 89,9 121,7 kW
Gas flow rate (min output) m³/h 2,2 2,1 2,45 m³/h

Domestic hot water performance

HeatMaster 70 TC Evo HeatMaster 85 TC Evo HeatMaster 120 TC Evo
Peak flow at 40°C L/10’ 716 783 900 L/10’
Peak flow 1st hour at 40°C L/60’ 2455 2895 3620 L/60’
Continuous flow at 40°C L/h 2087 2534 3402 L/h
Peak flow at 45°C L/10’ 592 646 676 L/10’
Peak flow 1st hour at 45°C L/60’ 2083 2456 3098 L/60’
Continuous flow at 45°C L/h 1789 2172 2928 L/h
Peak flow at 60°C L/10’ 348 371 440 L/10’
Peak flow 1st hour at 60°C L/60’ 1391 1638 1847 L/60’
Continuous flow at 60°C L/h 1252 1520 1754 L/h

Electrical Characteristics

HeatMaster 70 TC Evo HeatMaster 85 TC Evo HeatMaster 120 TC Evo
Voltage V 230 230 230 V
Frequency Hz 50 50 50 Hz
Protection IP 20 20 20
Electrical consumption W 210 266 327 W
Electrical power requirements A 1,4 1,7 2 A

Eco Design Fields

HeatMaster 70 TC Evo HeatMaster 85 TC Evo HeatMaster 120 TC Evo
Space heating energy efficiency class A A A
Seasonal space heating efficiency (35°C) % 93 92 92 %
Declared load profile XXL XXL XXL
Water heating energy efficiency class A A A
Water heating energy efficiency [ηwh] (EU 814/2013 Art 2 (15) Ann.IV-3) % 85,0 85 85 %
Sound power level indoors LWA dB 60 61 62 dB
Energy Label - -
Product Fiche

Technical brochure

ACVMax Touch - Installer's handboek for EVO appliances (2022 ->)

8.83MB – en

Evo Range Gas Conversion Procedure

2.28MB – fr en pl it de es ru

HeatMaster 25-35-45-70-85-120 TC Evo : Installation, operation and maintenance instructions

12.54MB – en

HeatMaster 25-35-45-70-85-120 TC Evo : Инструкции по монтажу, эксплуатации и техническому обслуживанию

12.67MB – ru

Safety Instructions - HeatMaster C/TC Evo - WaterMaster (X) Evo

2.85MB